SKU: 900112
Medicvent Central System Redundancy Module 360 consists of two exhaust fans, two frequency inverters, and an associated control cabinet, all mounted on a common chassis.
The fans are interconnected via a common duct system with non-return valves, allowing for easy removal of the fan in case of replacement during operation. The fans have been selected based on performance in terms of pressure curve and noise. The system is fully automatic and operates continuously. The system must be connected to a backup power supply according to ISO 16571:2024.
With two fans and regulation, the system achieves full redundancy. In the event of a failure of one fan or a malfunctioning frequency control, the system automatically switches the primary fan motor over to a secondary fan motor.
The central system for smoke evacuation, according to ISO standards, must always be 100% redundant.
Power:
400 V AC, 50Hz 3-phase
Automatic fuse (control cabinet)
2st 3-pol C10A
Power consumption:
5,1kW
System under pressure for anesthetic gases: -50hPa
0 – 560m³/hour (280m³/hour. vid 100 % redundans)
System under pressure for smoke gases: -100 hPa
0 – 500m³/h (250m³/h. vid 100 % redundans)
Sound level fan:
67dB(A)